What is the transformer protection TA disconnection criterion?

* Question

What is the transformer protection TA disconnection criterion?


*
Answer

1 When the zero-sequence current appears on the △ side of the transformer, it is judged that the TA is disconnected on the side;

2 on the Y side of the transformer, if it is an ordinary winding transformer, the zero-sequence current difference between the self-produced zero-sequence current and the neutral point TA of the transformer exceeds a certain value.A value, that is, the side TA is determined to be disconnected, and an alarm signal is delayed.